delivery contents:
Mains backup unit for emergency power supply as a backup power system with an original DEUTZ AG industrial diesel engine with electronic speed control and cooling water preheating (230 volts) and Stamford three-phase synchronous generator. Motor and generator are mounted elastically on a common skid frame.
Other additional features:
Tank capacity 360 liters, refueling directly at the tank
Fuel consumption at 100% load 50 liters/hour, sufficient for approx. 7.2 hours of operation
Fuel consumption at 75% load 40 litres/hour, sufficient for approx. 9 hours of operation
Fuel consumption at 50% load 28 litres/hour, sufficient for approx. 12.8 hours of operation
Internal automatic start-stop (type: AMF ComAp Intelygen 200) with display of all important engine and generator messages. Functional indication digitally on the display. 4-pin generator switch integrated on the unit (generator). Internal battery charger 230 volts - 12 volts DC
Automatic start, control of on-site external mains and generator switching
optional; External emergency power switchover for installation in the building and 4-pole mains generator switchover
Function: In the event of a power failure, the start command is sent to the diesel unit. When the nominal speed and nominal voltage are reached, the generator switch is switched on. When the mains returns, the automatic system monitors the mains voltage. When this is stable again, the switch back to mains operation takes place without interruption. The diesel unit is stopped after the cooling time and waits in automatic mode for the next power failure.
The emergency power system as an emergency power supply is ready for operation and immediately available from the Verl warehouse.