Emergency generator 40 kVA as backup generator BF 4 M 2011 in RAL 7046 telegrey 2 with 100 liter tank

stromerzeuger stromerzeuger stromerzeuger
Stock No.
1354
Language / Sprache
PDF Download
Overview / Übersicht

Completion:

Generating Set: 
stationary 

Gen Set: 
silent Set  

Technical Data Engine:

Engine Manufacturer:  
Deutz 

Engine Type:  
BF 4 M 2011 

Engine No.:  
auf Anfrage 

Engine Power:  
36,4 KW 

Cooling:  
oil-cooled 

Starting:  
electrical 12 V DC 

Rotation:  
1500 rpm 

Fuel:  
heating oil EN 590

Technical Data Generator:

Generator Manufacturer:  
Stamford AvK 

Gen Set:  
Synchron mit AVR 

Gen No.:  
auf Anfrage 

Gen Power:  
40 kVA 

Voltage:  
400 / 231 Volt 

Power Factor:  
cos. - phi 0,8 

Rotation:  
1500 rpm

Control Unit:

Setup: 
automatic start 

Functions: 
Hand & Remotestart 

Switch: 
gen switch 4 pole 

Delivery: 
set up 

Width ca. mm: 
 

Height ca. mm: 
 

Depth ca. mm: 
 

Fuel Tank:

Setup: 
Baseframe fuel Tank with Bassin 

Width ca. mm: 
 

Height ca. mm: 
 

Depth ca. mm: 
 

Capacity / Litre: 
100 

Dimensions of unit:

Width ca. mm: 
960 

Height ca. mm: 
1.430 

Length ca. mm: 
2.220 

Weigth ca. KG: 
1.050 

Usage:

Stock No: 
1354 

State: 
new 

year of manufacture: 
2023 

time of delivery: 
ex work 

Operating Hours: 

Location: 
Verl - Germany 

 
 

Price plus VAT in €: 
on request: 

 
 

Reserved: 
nein / no 

 
 

 
 

delivery contents:

General equipment Emergency generator TYPE WA DG 40 "S" 100 L | RAL 7046

Soundproof backup power supply with the following properties:

Emergency generator as backup power supply for your reliable emergency power supply with an original 4-cylinder Deutz industrial diesel engine with mechanical speed control and Stamford three-phase synchronous generator. Motor and generator are mounted elastically on a common skid frame. Exhaust system insulated with mineral fiber sheathing. Installed in a modular soundproofing enclosure. Powder-coated in RAL 7046 telegrey
-------------------------------------------------- -------------------------------------------------
Fuel consumption according to Deutz data sheet:
4.47 liters at 50% load | Running time with a full tank approx. 22.3 hours
6.66 liters at 75% load | Running time with a full tank approx. 15.0 hours
9.10 liters at 100% load | Running time with a full tank approx. 10.9 hours
-------------------------------------------------- -------------------------------------------------
Internal automatic start-stop (type: AMF DSE 4150) with display of all important engine and generator messages. Functional indication digitally on the display. Generator switch 63 amps 4 poles integrated in the unit (switchgear). Internal battery charger 230 volts - 12 volts DC

Optionally available at extra cost (1,620 euros net):

Automatic start with mains & generator switching 4-pin | 90 amps
External emergency power switchgear for installation in the building and 4-pole mains generator switchover
Function: In the event of a power failure, the start command is sent to the diesel unit. When the nominal speed and nominal voltage are reached, the generator switch is switched on. When the mains returns, the automatic system monitors the mains voltage. When this is stable again, the system switches back to mains operation. The diesel unit is stopped after the cooling time and waits in automatic mode for the next power failure.
-/-
Optional, available at extra cost: (subject to availability)

CEE socket 63 ampere 1H coded attached to the unit, this plug device is required for feeding into a building according to VDE 0100-551 supplement 1: 2019.06
VDE-AR-N 4100 contains additional requirements for setting up emergency power supplies for permanently installed systems (parts) that are supplied from the public grid during normal operation.
The emergency power system as an emergency power supply is ready for operation and immediately available from the Verl warehouse.

Stock No.
1354
Language / Sprache
PDF Download
Overview / Übersicht




Please use our formular for further information.


Name*: 
  
Company: 
E-Mail*: 
Street / No.: 
  
Zip-Code / City: 
  
Phone* / Fax: 
  
Message: 


Ich habe die Datenschutzerklärung zur Kenntnis genommen.
Ich stimme zu, dass meine Angaben und Daten zur Beantwortung meiner Anfrage elektronisch erhoben und gespeichert werden. Hinweis: Sie können Ihre Einwilligung jederzeit für die Zukunft per E-Mail an info@wa-strom.de widerrufen.