delivery contents:
Emergency generator as a mains backup system for the emergency power supply as a backup power system with an original Deutz industrial diesel engine with speed control and a Stamford three-phase synchronous generator. Motor and generator are mounted elastically on a common skid frame. Installed in a modular soundproofing enclosure.
Powder-coated in RAL 3000
Other additional features:
Tank capacity 50 liters, refueling directly at the tank
2.14 liters / hour at 25% load
4.07 liters / hour at 50% load
5.46 liters / hour at 75% load
7.18 liters / hour at 100% load
Internal automatic start-stop (type: AMF DSE 4150) with display of all engine and generator messages. Functional indication digitally on the display. Generator switch 40 amps 4 poles integrated in the unit (generator). Internal battery charger 230 volts - 12 volts DC
Optionally available at extra cost:
Automatic start with mains & generator switching 4-pole
External emergency power switchgear for installation in the building and 4-pole mains generator switchover
Function: In the event of a power failure, the start command is transferred to the diesel generator set. When the rated speed and rated voltage is replaced, the generator switch WILL be switched on. When the mains returns, the automatic system monitors the mains voltage. When this is stable again, the system switches back to mains operation. The diesel genset WILL be stopped after the cooling time and waits in automatic mode for the next power failure.
The emergency power system as an emergency power supply is ready for operation and immediately available from stock.